Inim 4 supervised In-/Output module, as supervised output or input, conventional zone,4-20 mA input.
1545 visitor(s) liked this product.
If you have any question please write to our colleagues!
Inim fire detection, Previdia IFM4IO. 4 supervised power Input/Output module. Each of the 4 channels can be configured as:
- supervised output capable of erogating a maximum current of 1 A @ 27.6 V, configurable;
- supervised input capable of activating warning, pre-alarm and alarm signals, configurable;
- conventional zone capable of managing a line of conventional detectors, maximum 32 detectors, configurable;
- 4...20 mA input capable of reading 4...20 mA detector signals; settable intervention thresholds; configurable.
Each control panel can manage a maximum of 16 IFM4IO modules.
Technical specifications:
- Power supply voltage: 19...30 V DC,
- Operating temperature: -5 °C ... +40 °C,
- Consumption @ 27.6 V: 22...170 mA,
- Maximum voltage on outputs: 1 A @ 27.6 V.